The process of recovering factory defaults deletes all platform and station data, and returns the controller to the state it was in when it shipped from the factory. If you cannot commission the controller because you made an error when entering the default platform daemon credentials or passphrase, you can restore factory defaults and start again. Also, when decommissioning a controller, a best practice is to recover the factory defaults, which removes the platform and station data from the controller. This procedure uses a terminal emulator program to access the controller’s system shell menu.

To reset a SLX-9000 to factory default state:

  • You have backed up all data from the controller.

  • If you are planning a “power—on” reboot using the serial shell menu (a) The controller’s DEBUG port is connected to your PC using a USB-to-micro USB cable. (b) Power is currently applied to the controller.

  • You are logged into to the controller serial shell using a terminal emulator (system shell program), such as PuTTY and the serial shell menu is visible on your PC. CAUTION! Recovering factory defaults removes all platform and station data from the device. Make sure this is what you intend before you follow this procedure.

  1. With the outer panel cover open, press and hold the SHUT DOWN button on the SLX-9000 control panel.

  1. While still pressing the SHUT DOWN button, reboot the controller by either adding power to a powered off controller OR choosing option 9, Reboot, from the serial shell menu and entering “Y” at the confirmation prompt, upon which reboot is initiated.

  1. Release the SHUT DOWN button 5 seconds after reboot is initiated. Factory default restoration process begins.

  • When the BEAT LED blinks at a normal rate, the process is complete. NOTICE! To setup the restored controller platform you will need to login to the serial shell using factory default credentials.

恢复出厂设置(SLX-9000)

恢复出厂默认设置的过程将删除所有平台和站点数据,并将控制器恢复到出厂时的状态。如果您因为输入默认平台守护程序凭据或密码时出错而无法启用控制器,您可以恢复出厂设置并重新开始。此外,在停用控制器时,最佳实践是恢复出厂设置,这样可以从控制器中移除平台和站点数据。此过程使用终端仿真程序来访问控制器的系统壳菜单。

要将SLX-9000重置为出厂默认状态,请按照以下步骤操作:

您已从控制器备份所有数据。

如果您计划使用串行壳菜单进行“开机”重启(a)控制器的DEBUG端口通过USB-to-micro USB电缆连接到您的PC。(b)控制器当前已接通电源。

您已使用终端仿真器(系统壳程序)如PuTTY登录到控制器串行壳,并且串行壳菜单已显示在您的PC上。警告!恢复出厂设置将删除设备上的所有平台和站点数据。在您按照此程序操作之前,请确保这是您的意图。

打开外部面板盖,按下并保持SLX-9000控制面板上的关机按钮。

在按下关机按钮的同时,通过以下方式重新启动控制器:给处于关机状态的控制器通电,或者从串行壳菜单中选择选项9,重启,并在确认提示时输入“Y”,随后将开始重启。

在启动重启后5秒释放关机按钮。出厂默认恢复过程开始。

当BEAT LED以正常速率闪烁时,过程完成。注意!要设置恢复后的控制器平台,您需要使用出厂默认凭据登录到串行壳。